Tilda Publishing

MURAWAY

Tilda Publishing

Fire extinguishing gas module - AUTOMATIC type

Fire extinguishing gas module - high pressure metal cylinder with a charge of liquid carbon dioxide (according to GOST 8050-85) under the pressure of saturated vapor.

The work of the Module is based on the drive out of the carbon dioxide under the influence of its own excess pressure, which is created when the module is filled. The fire-extinguishing effect of carbon dioxide is based on cooling the fire zone and diluting the combustible vapor-air medium with an inert (non-combustible) substance, lowing its concentrations at levels where the combustion reaction stops.

The Module is designed to extinguish fires of various substances, the combustion of which cannot occur without oxygen access, fires on electrified railway and city transport, electrical equipment up to 10 kV, fires in museums, art galleries and archives, in offices and residential sector.

The start of the Module is provided by the initiation device installed on the neck of the cylinder.
The start signal ought to be provided from the antifire automations.

Manufatured in accordance with Organization Standard 4854-014-13525135-2014.
Technical specifications

s/n
Parameter
Unit
Value
Maximum protected volume
m3
from 0.3 to 10.0
1
kg
2
Liquid gas weight
from 0.2 to 14.25
Operating pressure
Testing pressure
Membrane safe locker activation pressure
Nominal diameter of the start-stop device
Sizes Length х Width х Height
Operating temperature
Cylinder weight
95 % mass gas escape duration
Remaining gas weight after module activation and fire extinguishing
Cylinder life time
Module recharge, every
3
4
5
6
8
9
10
11
12
13
14
MPa
MPa
MPa
mm
mm
°С
kg
s
kg
year
year
6.0
22.5
15
3.1
from 40х40х380 to 159x159x1280
from – 40 to + 50
from 0.85 to 26.40
from 10 to 60
from 0.05 tp 0.10
15
5
7
Starter tipe
-
squib or electromagnetic drive
Cylinder inspection frequency
15
year
10
Connecting thread cylinder-activator
16
-
М18Х1.5
Activation voltage
17
V
from 10 to 26
Activation current
18
A
0.5
Current impulse duration
19
ms
8
Circuit resistance
20
Om
from 1.5 to 4.0
Electric current strength for circuit resistance control
21
A
0.05 (duration 5 minutes)
Muraway test
© 2021 "PIROCHIMICA" LLC
115088, MOSCOW,
SHARIKOPODSHIPNIKOVSKAYA 4
TEL. +7 (499) 579-83-75
E-MAIL: INFO@PIROHIM.RU
PRODUCTION
EN